Display |
Identifier |
Values |
Description |
Det |
Control unit detector |
|
When the set values are reached, a message is output, or the defined reaction is triggered. |
|
|
|
|
|
|
List |
All parallel detectors of the basic supply. |
Occupancy: Threshold 1 |
Occupancy time for threshold 1 |
|
Sending a message to the control unit (vs | plus error message 20) after threshold 1 has been reached. |
|
|
|
|
|
|
0 .. 3200 |
Time in seconds |
Occupancy: Threshold 2 |
Occupancy time for threshold 2 |
|
After reaching threshold 2, the defined reaction is triggered. |
|
|
|
|
|
|
0 .. 3200 |
Time in seconds |
Reaction |
Reaction |
|
Reaction to reaching threshold 2 |
|
|
|
|
|
|
Cancel |
|
|
|
Controller in cyclic mode |
|
|
|
Send message |
|
|
|
Switch off whole controller |
|
|
|
Switch off partial intersection 1 |
|
|
|
Switch off partial intersection 2 |
|
|
|
Switch off partial intersection 3 |
|
|
|
Switch program according to YAUT |
|
|
|
Switch to pre-configured emergency program |
|
|
|
Reset vs | plus |
|
Gap: Threshold 1 |
Threshold 1 for gap |
|
Sending a message to the control unit (vs | plus error message 21) after threshold 1 has been reached. |
|
|
|
|
|
|
0 .. 3200 |
Time in seconds |
Gap: Threshold 2 |
Threshold 2 for gap |
|
After reaching threshold 2, the defined reaction is triggered. . |
|
|
|
|
|
|
0 .. 3200 |
Time in seconds |
Reaction |
Reaction |
|
Reaction to reaching threshold 2 |
|
|
|
|
|
|
Cancel |
|
|
|
Controller in cyclic mode |
|
|
|
Send message |
|
|
|
Switch off whole controller |
|
|
|
Switch off partial intersection 1 |
|
|
|
Switch off partial intersection 2 |
|
|
|
Switch off partial intersection 3 |
|
|
|
Switch program according to YAUT |
|
|
|
Switch to pre-configured emergency program |
|
|
|
Reset vs | plus |